Overvoltage during deceleration means the deceleration time is too short, an overhauling load is present, or the input voltage is fluctuating abnormally. The manual's first action is: “Increase the deceleration time parameters (DEC or FSOI).”
- Model
- Schneider Electric Altivar 21
- Display shows
- Overvoltage during deceleration (OP2)
- Type
- Fault code
- Source
- Manual p. 120
What OP2 means
Overvoltage during deceleration p. 120
Common causes
- The deceleration time is too short. p. 120
- Overhauling load p. 120
- The input voltage is fluctuating abnormally. p. 120
- Power network is greater than 200 kVA p. 120
- Power factor capacitor switching p. 120
- SCR switching on power network p. 120
- The drive is starting into a rotating load. p. 120
- Intermittent output phase fault p. 120
What to do
- Increase the deceleration time parameters (DEC or FSOI). p. 120
- Enable parameter F305. p. 120
- Install a line reactor. p. 120
- Check the input and output circuits for phase failure and rectify. p. 120
- Enable catch on the fly, parameter F301. p. 120
Before you service the product, read the safety instructions in the manual p. 5.
If OP2 is still not resolved
This page summarises what the manufacturer’s manual says about OP2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.