Overcurrent during acceleration means the acceleration time is too short, the setting of parameter PEL is incorrect, or the drive is starting into a rotating load. The manual's first action is: “Increase the acceleration time parameters (ACC or F500).”
- Model
- Schneider Electric Altivar 21
- Display shows
- Overcurrent during acceleration (OC1)
- Type
- Fault code
- Source
- Manual p. 119
What OC1 means
Overcurrent during acceleration p. 119
Common causes
- The acceleration time is too short. p. 119
- The setting of parameter PEL is incorrect. p. 119
- The drive is starting into a rotating load. p. 119
- The drive is powering a low impedance motor. p. 119
- Ground fault p. 119
What to do
- Increase the acceleration time parameters (ACC or F500). p. 119
- Select the correct setting for parameter PEL. p. 119
- Enable catch on the fly, parameter F301. p. 119
- Adjust the switching frequency parameter F300. p. 119
- Set parameter F316 to 1 or 3. p. 119
Before you service the product, read the safety instructions in the manual p. 5.
If OC1 is still not resolved
This page summarises what the manufacturer’s manual says about OC1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.