Schneider Electric Altivar 21 Error OC1: Overcurrent during acceleration

Altivar 21 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeOC1

Overcurrent during acceleration means the acceleration time is too short, the setting of parameter PEL is incorrect, or the drive is starting into a rotating load. The manual's first action is: “Increase the acceleration time parameters (ACC or F500).”

Model
Schneider Electric Altivar 21
Display shows
Overcurrent during acceleration (OC1)
Type
Fault code
Source
Manual p. 119

What OC1 means

Overcurrent during acceleration p. 119

Common causes

  • The acceleration time is too short. p. 119
  • The setting of parameter PEL is incorrect. p. 119
  • The drive is starting into a rotating load. p. 119
  • The drive is powering a low impedance motor. p. 119
  • Ground fault p. 119

What to do

  1. Increase the acceleration time parameters (ACC or F500). p. 119
  2. Select the correct setting for parameter PEL. p. 119
  3. Enable catch on the fly, parameter F301. p. 119
  4. Adjust the switching frequency parameter F300. p. 119
  5. Set parameter F316 to 1 or 3. p. 119

Before you service the product, read the safety instructions in the manual p. 5.

If OC1 is still not resolved

  • contact Schneider Electric service p. 5
    “Schneider Electric accepts no responsibility for the consequences of using this device”
  • contact a qualified technician p. 6
    “Installation, adjustment, repair, and maintenance must be performed by qualified personnel”

This page summarises what the manufacturer’s manual says about OC1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.