Schneider Electric Altivar 21 Error OP1: Overvoltage during acceleration

Altivar 21 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeOP1

Overvoltage during acceleration means the input voltage is fluctuating abnormally, the power network is greater than 200 kVA, or power factor capacitor switching is occurring. The manual's first action is: “Install a line reactor.”

Model
Schneider Electric Altivar 21
Display shows
Overvoltage during acceleration (OP1)
Type
Fault code
Source
Manual p. 120

What OP1 means

Overvoltage during acceleration p. 120

Common causes

  • The input voltage is fluctuating abnormally. p. 120
  • Power network is greater than 200 kVA. p. 120
  • Power factor capacitor switching p. 120
  • SCR switching on power network p. 120
  • The drive is starting into a rotating load. p. 120
  • Intermittent output phase fault p. 120

What to do

  1. Install a line reactor. p. 120
  2. Enable catch on the fly, parameter F301. p. 120
  3. Set parameter F302 to 2. p. 120
  4. Determine the cause of the missing output phase (such as a bad connection, an output disconnect, or an open winding in the motor) and rectify the problem. p. 120

Before you service the product, read the safety instructions in the manual p. 5.

If OP1 is still not resolved

  • contact Schneider Electric service p. 5
    “Schneider Electric accepts no responsibility for the consequences of using this device”
  • contact a qualified technician p. 6
    “Installation, adjustment, repair, and maintenance must be performed by qualified personnel”

This page summarises what the manufacturer’s manual says about OP1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.