Schneider Electric Altivar 21 Error OC2: Overcurrent during deceleration

Altivar 21 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeOC2

Overcurrent during deceleration means the deceleration time is too short or a ground fault occurred. The manual's first action is: “Increase the deceleration time parameters (DEC or F501).”

Model
Schneider Electric Altivar 21
Display shows
Overcurrent during deceleration (OC2)
Type
Fault code
Source
Manual p. 119

What OC2 means

Overcurrent during deceleration p. 119

Common causes

  • The deceleration time is too short. p. 119
  • Ground fault p. 119

What to do

  1. Increase the deceleration time parameters (DEC or F501). p. 119
  2. Set parameter F316 to 1 or 3. p. 119

Before you service the product, read the safety instructions in the manual p. 5.

If OC2 is still not resolved

  • contact Schneider Electric service p. 5
    “Schneider Electric accepts no responsibility for the consequences of using this device”
  • contact a qualified technician p. 6
    “Installation, adjustment, repair, and maintenance must be performed by qualified personnel”

This page summarises what the manufacturer’s manual says about OC2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.