Fault codeEEn1
Auto-tuning error means parameters F401 to F494 are incorrectly set, the motor is too large for the drive, or the motor cable gauge is too small. The manual's first action is: “Set parameters F401-F494 correctly.”
- Model
- Schneider Electric Altivar 21
- Display shows
- Auto-tuning error (EEn1)
- Type
- Fault code
- Source
- Manual p. 119
What EEn1 means
Auto-tuning error p. 119
Common causes
- Parameters F401 to F494 are incorrectly set. p. 119
- The motor is too large for the drive. p. 119
- The motor cable gauge is too small. p. 119
- The motor is still rotating at the start of the auto-tune. p. 119
- The drive is not powering a 3-phase induction motor. p. 119
What to do
- Set parameters F401-F494 correctly. p. 119
- Use a larger drive. p. 119
- Use a larger gauge motor cable. p. 119
- Verify that the motor is stopped before starting an auto-tune. p. 119
- Use the drive to power only a 3-phase induction motor. p. 119
Before you service the product, read the safety instructions in the manual p. 5.
If EEn1 is still not resolved
This page summarises what the manufacturer’s manual says about EEn1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.