Schneider Electric Altivar 21 Error EEn1: Auto-tuning error

Altivar 21 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeEEn1

Auto-tuning error means parameters F401 to F494 are incorrectly set, the motor is too large for the drive, or the motor cable gauge is too small. The manual's first action is: “Set parameters F401-F494 correctly.”

Model
Schneider Electric Altivar 21
Display shows
Auto-tuning error (EEn1)
Type
Fault code
Source
Manual p. 119

What EEn1 means

Auto-tuning error p. 119

Common causes

  • Parameters F401 to F494 are incorrectly set. p. 119
  • The motor is too large for the drive. p. 119
  • The motor cable gauge is too small. p. 119
  • The motor is still rotating at the start of the auto-tune. p. 119
  • The drive is not powering a 3-phase induction motor. p. 119

What to do

  1. Set parameters F401-F494 correctly. p. 119
  2. Use a larger drive. p. 119
  3. Use a larger gauge motor cable. p. 119
  4. Verify that the motor is stopped before starting an auto-tune. p. 119
  5. Use the drive to power only a 3-phase induction motor. p. 119

Before you service the product, read the safety instructions in the manual p. 5.

If EEn1 is still not resolved

  • contact Schneider Electric service p. 5
    “Schneider Electric accepts no responsibility for the consequences of using this device”
  • contact a qualified technician p. 6
    “Installation, adjustment, repair, and maintenance must be performed by qualified personnel”

This page summarises what the manufacturer’s manual says about EEn1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.