Schneider Altivar 12 Error SPIF: PI Feedback detected fault

Altivar 12 variable speed drive · taken from the manufacturer’s manual, pages cited

Fault codeSPIF

PI Feedback detected fault indicates a PID feedback below the lower limit. The manual's first action is: “Check the PID function feedback.”

Model
Schneider Altivar 12
Display shows
PI Feedback detected fault (SPIF)
Type
Fault code
Source
Manual p. 110

What SPIF means

PI Feedback detected fault p. 110

Common causes

  • PID feedback below lower limit p. 110

What to do

  1. Check the PID function feedback. p. 110
  2. Check the PI feedback supervision threshold LPI and time delay LPI, page 76. p. 110

Before you service the product, read the safety instructions in the manual p. 4.

If SPIF is still not resolved

  • contact your local Schneider Electric representative p. 5
    “contact your local Schneider Electric representative. Do not repair or operate the drive.”

This page summarises what the manufacturer’s manual says about SPIF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.