The Analog Command Overvoltage code indicates the voltage applied to the analog speed command terminal SPR exceeds the value set by parameter Pr71. The manual's first action is: “Set parameter Pr71 (analog command deviation level) correctly. Check the wiring of connector X5. Increase the setting of parameter Pr57 (speed command filter). Set Pr71 to 0 to disable this protection function.”
- Model
- Panasonic Minas A4
- Display shows
- Analog Command Overvoltage (39)
- Type
- Error code
- Source
- Manual p. 65
What 39 means
Analog Command Overvoltage p. 65
Common causes
- The voltage applied to the analog speed command terminal SPR (X5 pin 14) exceeds the value set by parameter Pr71. This protection function operates only when there is an input on SPR/TRQR/SPL. It works more precisely when the following conditions are met: 1) Speed control mode with Pr02 = 1, 3, or 5, and Pr05 = 0 or 2 (analog command input selected) and the zero‑speed flag is invalid (speed command is not zero). 2) Torque control mode with Pr02 = 2 or 4, and Pr5B = 0. 3) Torque control mode with Pr02 = 2, 4, or 5, and Pr5B = 1, and the zero‑speed flag is invalid (speed command is not zero). p. 65
What to do
- Set parameter Pr71 (analog command deviation level) correctly. Check the wiring of connector X5. Increase the setting of parameter Pr57 (speed command filter). Set Pr71 to 0 to disable this protection function. p. 65
Before you service the product, read the safety instructions in the manual p. 72.
If 39 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Panasonic service.
This page summarises what the manufacturer’s manual says about 39; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Panasonic. Found a mistake? Report an error.