The Control Power Undervoltage code indicates the voltage between P and N on the control power inverter is below the specified value. The manual's first action is: “Measure the voltage between L1C, L2C and r, t.”
- Model
- Panasonic Minas A4
- Display shows
- Control Power Undervoltage (11)
- Type
- Error code
- Source
- Manual p. 62
What 11 means
Control Power Undervoltage p. 62
Common causes
- The voltage between P and N on the control power inverter is below the specified value. p. 62
- 1) The AC supply voltage is too low, causing a momentary power loss. p. 62
- 2) The power supply capacity is too small. p. 62
- The inrush current at power-on causes a voltage drop. p. 62
- 3) The driver (internal circuitry) is defective. p. 62
What to do
- Measure the voltage between L1C, L2C and r, t. p. 62
- 1) Increase the supply voltage. Replace the power supply. p. 62
- 2) Increase the power supply capacity. p. 62
- 3) Replace with a new driver. p. 62
Before you service the product, read the safety instructions in the manual p. 72.
If 11 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Panasonic service.
This page summarises what the manufacturer’s manual says about 11; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Panasonic. Found a mistake? Report an error.