Error, fault and alarm codes of products - what each code means, its causes and what to do - read from the manufacturers’ manuals, with the manual page each answer comes from.
The capacitor bank has experienced overvoltage conditions. The manual lists no action for this code.
The capacitor pre-charge process failed, preventing normal operation. The manual lists no action for this code.
Temperature sensor 2 has detected a fault or malfunction. The manual lists no action for this code.
Temperature sensor 1 has detected a fault or malfunction. The manual lists no action for this code.
Manual bypass mode is active, requiring user intervention to exit it. The manual's first action is: “To exit manual bypass mode, press the ON+SEL buttons at the same time for at least 4 seconds.”
A remote command has been activated, causing the system to switch off remotely. The manual's first action is: “If unwanted, check the status of the command inputs on any optional contact card.”
The UPS is malfunctioning due to battery overvoltage conditions. The manual's first action is: “If possible, disconnect the power to the load, switch the UPS off and back on again; if the problem occurs again, call th…
There is a short circuit on one or more utilities powered by the UPS. The manual's first action is: “Disconnect all the utilities, switch the UPS off and back on again, reconnect the utilities one at a time to identif…
The internal dissipators inside the UPS have exceeded their maximum temperature limit. The manual's first action is: “Check that the temperature of the environment in which the UPS is located does not exceed 40°C.”
The UPS is malfunctioning and may lock soon due to incorrect auxiliary power supply. The manual's first action is: “If possible, disconnect the power to the load, switch the UPS off and back on again; if the problem o…
The batteries are flat and the UPS is waiting for voltage to recover above threshold. The manual's first action is: “Wait until the batteries have recharged or force power-on manually by holding down the "ON" button f…
The battery box is missing or not connected, preventing proper battery operation. The manual's first action is: “On the versions with an additional battery charger in place of the batteries, check that the Battery Box…
The batteries need replacement due to failure or degradation. The manual's first action is: “Contact the support centre for battery replacement.”
The load applied to the UPS exceeds the user-set threshold, causing overload conditions. The manual's first action is: “Reduce the load to within the threshold of 100% (for user threshold in the case of code A54). If …
The control card is not inserted correctly into the UPS unit. The manual's first action is: “Switch off and disconnect the UPS from the power supply and contact the support centre.”