Error, fault and alarm codes of products - what each code means, its causes and what to do - read from the manufacturers’ manuals, with the manual page each answer comes from.
Feedforward bias FF is out of the valid range (-6383 to +6383), causing an error. The manual's first action is: “Change FF so it is within the range -6383...+6383.”
Derivative gain rate Td is set to a negative value, which is invalid for control operation. The manual's first action is: “Change derivative gain (rate) Td to 0 ≤ Td”
Integral gain reset time T1 is set to a negative value, which is invalid for control operation. The manual's first action is: “Change integral gain (reset) T1 to 0 ≤ T1”
Proportional gain Kc is set to a negative value, which is invalid for control operation. The manual's first action is: “Change proportional gain Kc to 0 < Kc”
Loop update time O1 is out of range (0 or greater than 1024), requiring adjustment. The manual's first action is: “Change loop update time 0 < O1 ≤ 1024”
Total output pulses to be generated are invalid or communications channel is shut down, causing a controller fault. The manual's first action is: “Reconfigure the channel and retry operation.”
The jog frequency value exceeds valid limits, causing a controller fault. The manual lists no action for this code.
No error is present when a hard stop is detected, and it does not fault the controller. The manual's first action is: “To clear this error, scan the PTOX instruction on a false rung and reset the EH (Enable Hard Stop)…
An invalid output (not 2, 3, or 4) has been specified, causing a configuration error that faults the controller. The manual's first action is: “Output 2, output 3, and output 4 are the only valid choices. This is a co…
Multiple functions are assigned to the same physical output, causing a configuration error that faults the controller. The manual's first action is: “The controller faults and the User Fault Routine do not execute. Ex…
Acceleration and deceleration counts are not defined when Accel/Decel Pulses Independent is set to 1. The manual lists no action for this code.
Low preset underflow or multiple jog states are active, causing an error without controller fault. The manual's first action is: “Reconfigure the channel and retry operation.”
The accelerator/decelerate parameters exceed limits or overflow conditions occur, causing a controller fault. The manual lists no action for this code.
Acceleration and deceleration counts are not defined when Accel/Decel Pulses Independent is set to 1. The manual's first action is: “Check the modem and modem connections.”
Multiple functions are assigned to the same physical output, causing a configuration error that faults the controller. The manual's first action is: “The forced condition must be removed. This error does not fault the…