Omron CS1W-LCB01 and CS1W-LCB05 Error 11: Backup Data (Flash Memory) Error Flag

Omron CS1W-LCB01 and CS1W-LCB05 Loop Control Board · taken from the manufacturer’s manual, pages cited

Error code11

The parameter data stored in flash memory has been corrupted. The manual's first action is: “Output becomes the maximum value or minimum value of the output range. (For example, when the output range is ±320.00, the output becomes +320.00 or 320.00.) Check the ranges of the argument and results and correct the condition or operation so that the allowable ranges are not exceeded.”

Model
Omron CS1W-LCB01 and CS1W-LCB05
Display shows
Backup Data (Flash Memory) Error Flag (11)
Type
Error code
Source
Manual p. 115

What 11 means

Backup Data (Flash Memory) Error Flag p. 185

Common causes

  • The parameter data stored in flash memory has been corrupted. p. 185
  • The output value of the operation result exceeded the data length of two bytes. Note: An error does not occur even if the output range (±320.00, e.g.) is exceeded if the data length of two bytes is not exceeded. p. 185
  • The argument or results of operation in an Arithmetic Operation block (Block Model 126) exceeded the allowable range. p. 185

What to do

  1. Output becomes the maximum value or minimum value of the output range. (For example, when the output range is ±320.00, the output becomes +320.00 or 320.00.) Check the ranges of the argument and results and correct the condition or operation so that the allowable ranges are not exceeded. p. 185
  2. Execution of the Arithmetic Operation block will be stopped. Check the ranges of the arguments and correct the condition or calculation expressions. p. 185

Before you service the product, read the safety instructions in the manual p. 11.

If 11 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.

This page summarises what the manufacturer’s manual says about 11; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.