The LCB load rate exceeds 80% for three consecutive cycles. The manual's first action is: “If this error occurs, extend the operation cycles of function blocks that can be extended. If the error recurs after extending the operation cycles, add a Loop Control Unit and divert some of the load to that Unit.”
- Model
- Omron CS1W-LCB01 and CS1W-LCB05
- Display shows
- Loop Control Board High Load Flag (non-fatal error) (08)
- Type
- Error code
- Source
- Manual p. 115
What 08 means
Loop Control Board High Load Flag (non-fatal error) p. 115
Common causes
- The LCB load rate exceeds 80% for three consecutive cycles. p. 115
What to do
- If this error occurs, extend the operation cycles of function blocks that can be extended. If the error recurs after extending the operation cycles, add a Loop Control Unit and divert some of the load to that Unit. p. 115
Before you service the product, read the safety instructions in the manual p. 11.
If 08 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about 08; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.