Error codeAL11
Surroundings temperature, Continuous Overload alaram, Motor cable open The manual's first action is: “Check whether surrounding temperature is over 50 [C]”
- Model
- LS Mecapion L7P INDEXER Series
- Display shows
- Regeneration overload IPM temperature (AL11)
- Type
- Error code
- Source
- Manual p. 269
What AL11 means
Regeneration overload IPM temperature p. 269
Common causes
- surroundings temperature p. 269
- Continuous Overload alaram p. 269
- Motor cable open p. 269
- Drive setting direction p. 269
What to do
- Check whether surrounding temperature is over 50 [C] p. 269
- Accumulated operate overload percentage [0x2803] Checking the load percentage is under 100% p. 269
- Check accumulated regenerative overload[0x2606] p. 269
- Check drive setting status p. 269
If AL11 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact LS Mecapion service.
This page summarises what the manufacturer’s manual says about AL11; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with LS Mecapion. Found a mistake? Report an error.