INVT DA180 Error Er07-0: Regeneration discharge overload fault

AC servo drive · taken from the manufacturer’s manual, pages cited

Fault codeEr07-0

Regeneration discharge overload occurs due to low brake resistor power, high motor speed, or rapid deceleration. The manual's first action is: “7100-0700h”

Model
INVT DA180
Display shows
Regeneration discharge overload fault (Er07-0)
Type
Fault code
Source
Manual p. 258

What Er07-0 means

Regeneration discharge overload fault p. 258

Common causes

  • 1. The brake resistor power is low. 2. The motor speed is too high or the deceleration is too quick, which causes the failure to absorb the regenerative energy within specified time. 3. The action limit of the external brake resistor is restricted to the duty ratio 10%. p. 258
  • • p. 258

What to do

  1. 7100-0700h p. 258
  2. 1. Replace the internal brake resistor with an external one and increase the power. 2. Modify the deceleration time and reduce the regenerative discharge action rate. 3. Reduce the motor speed. 4. Improve the capacity of the motor and drive. p. 258

If Er07-0 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact INVT service.

This page summarises what the manufacturer’s manual says about Er07-0; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with INVT. Found a mistake? Report an error.