Overload means the drive is detecting excessive output current. The manual's first action is: “Check for correct settings at Pr. 06-06 and 06-07. If yes, check if load is too large. If yes, reduce load or increase the power of AC motor drive. If no, modify setting. If not, contact DELTA.”
- Model
- Delta VFD-M-D
- Display shows
- Overload (OL)
- Type
- Error code
- Source
- Manual p. 133
What OL means
Overload p. 133
Common causes
- OL1/OL2 p. 133
- The AC motor drive detects excessive drive output current. NOTE: The AC motor drive can withstand up to 150% of the rated current for a maximum of 60 seconds. p. 133
What to do
- Check for correct settings at Pr. 06-06 and 06-07. If yes, check if load is too large. If yes, reduce load or increase the power of AC motor drive. If no, modify setting. If not, contact DELTA. p. 133
- 1. Check whether the motor is overloaded. 2. Reduce torque compensation setting in Pr.2-03. 3. Use the next higher power AC motor drive model. p. 133
Before you service the product, read the safety instructions in the manual p. 4.
If OL is still not resolved
- contact your dealer p. 4 “If you have any questions, please contact your dealer.”
This page summarises what the manufacturer’s manual says about OL; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.