Delta VFD-M-D Error OL: Overload

VFD-M-D AC motor drive · taken from the manufacturer’s manual, pages cited

Error codeOL

Overload means the drive is detecting excessive output current. The manual's first action is: “Check for correct settings at Pr. 06-06 and 06-07. If yes, check if load is too large. If yes, reduce load or increase the power of AC motor drive. If no, modify setting. If not, contact DELTA.”

Model
Delta VFD-M-D
Display shows
Overload (OL)
Type
Error code
Source
Manual p. 133

What OL means

Overload p. 133

Common causes

  • OL1/OL2 p. 133
  • The AC motor drive detects excessive drive output current. NOTE: The AC motor drive can withstand up to 150% of the rated current for a maximum of 60 seconds. p. 133

What to do

  1. Check for correct settings at Pr. 06-06 and 06-07. If yes, check if load is too large. If yes, reduce load or increase the power of AC motor drive. If no, modify setting. If not, contact DELTA. p. 133
  2. 1. Check whether the motor is overloaded. 2. Reduce torque compensation setting in Pr.2-03. 3. Use the next higher power AC motor drive model. p. 133

Before you service the product, read the safety instructions in the manual p. 4.

If OL is still not resolved

  • contact your dealer p. 4
    “If you have any questions, please contact your dealer.”

This page summarises what the manufacturer’s manual says about OL; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.