Fault codeOC
Over current means the drive is drawing more current than it can handle. The manual's first action is: “Yes”
- Model
- Delta VFD-M-D
- Display shows
- Over current (OC)
- Type
- Fault code
- Source
- Manual p. 130
What OC means
Over current p. 130
Common causes
- Has load changed suddenly? p. 130
- Reduce load or increase the power of AC motor drive p. 130
- Abnormal increase in current. p. 130
What to do
- Yes p. 130
- 1. Check if motor power corresponds with the AC motor drive output power. 2. Check the wiring connections to U, V, W for possible short circuits. 3. Check the wiring connections between the AC motor drive and motor for possible short circuits, also to ground. 4. Check for loose contacts between AC motor drive and motor. 5. Increase the Acceleration Time. 6. Check for possible excessive loading conditions at the motor. 7. If there are still any abnormal conditions when operating the AC motor drive after a short-circuit is removed and the other points above are checked, it should be sent back to manufacturer. p. 130
Before you service the product, read the safety instructions in the manual p. 4.
If OC is still not resolved
- contact your dealer p. 4 “If you have any questions, please contact your dealer.”
This page summarises what the manufacturer’s manual says about OC; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.