Fault codeocA
Over-current during acceleration means the drive is drawing too much current while accelerating. The manual's first action is: “Yes”
- Model
- Delta VFD-M-D
- Display shows
- Over-current during acceleration (ocA)
- Type
- Fault code
- Source
- Manual p. 130
What ocA means
Over-current during acceleration p. 130
Common causes
- Remove short circuit or ground fault p. 130
- Check if there is any short circuits and grounding between the U, V, W and motor p. 130
- Check if load is too large p. 130
- Reduce torque compensation p. 130
- Check if acceleration time is too short by load inertia p. 130
- Maybe AC motor drive has malfunction or error due to noise. Please contact with DELTA. p. 130
- Can acceleration time be made longer? p. 130
- Increase accel/decel time p. 130
- Can deceleration time be made longer? p. 130
- Reduce load or increase the power of AC motor drive p. 130
- Check braking method. Please contact DELTA p. 130
What to do
- Yes p. 130
- No p. 130
- 1. Short-circuit at motor output: Check for possible poor insulation at the output lines. 2. Torque boost too high: Decrease the torque compensation setting in Pr.2-01. 3. Acceleration Time too short: Increase the Acceleration Time. 4. AC motor drive output power is too small: Replace the AC motor drive with the next higher power model. p. 130
Before you service the product, read the safety instructions in the manual p. 4.
If ocA is still not resolved
- contact your dealer p. 4 “If you have any questions, please contact your dealer.”
This page summarises what the manufacturer’s manual says about ocA; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.