Fault codeID 10
Overvoltage (Hardware Fault) occurs when the DC link voltage exceeds limits, due to too short deceleration time or high overvoltage spikes. The manual's first action is: “Set the deceleration time longer (P3.4.1.3 and P3.4.2.3).”
- Model
- Danfoss 100 FLOW
- Display shows
- Overvoltage (Hardware Fault) (ID 10)
- Type
- Fault code
- Source
- Manual p. 293
What ID 10 means
Overvoltage (Hardware Fault) p. 293
Common causes
- The DC link voltage is higher than the limits. p. 293
- too short a deceleration time p. 293
- high overvoltage spikes in the supply p. 293
What to do
- Set the deceleration time longer (P3.4.1.3 and P3.4.2.3). p. 293
- Activate the overvoltage controller. p. 293
- Check the input voltage. p. 293
If ID 10 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Danfoss service.
This page summarises what the manufacturer’s manual says about ID 10; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Danfoss. Found a mistake? Report an error.