ABB ACS850 Error 2012: BC OVERHEAT (0x7181)

ABB ACS850 · taken from the manufacturer’s manual, pages cited

Alarm code2012

BC OVERHEAT (0x7181) means the brake chopper IGBT temperature exceeded the internal alarm limit. The manual's first action is: “Cool the chopper down. Check if the ambient temperature is too high. Inspect the cooling fan for faults. Ensure there is no obstruction to airflow. Verify cabinet size and cooling performance. Check the brake resistor overload protection settings (parameters 48.01…48.05). Verify that the braking cycle meets allowed limits. Check whether the inverter's AC supply voltage exceeds the permissible range.”

Model
ABB ACS850
Display shows
BC OVERHEAT (0x7181) (2012)
Type
Alarm code
Source
Manual p. 284

What 2012 means

BC OVERHEAT (0x7181) p. 284

Common causes

  • The brake chopper IGBT temperature exceeds the internal alarm limit. p. 284

What to do

  1. Cool the chopper down. Check if the ambient temperature is too high. Inspect the cooling fan for faults. Ensure there is no obstruction to airflow. Verify cabinet size and cooling performance. Check the brake resistor overload protection settings (parameters 48.01…48.05). Verify that the braking cycle meets allowed limits. Check whether the inverter's AC supply voltage exceeds the permissible range. p. 284

Before you service the product, read the safety instructions in the manual p. 179.

If 2012 is still not resolved

  • 请联系当地的 ABB 代表 p. 296
    “请联系当地的 ABB 代表”

This page summarises what the manufacturer’s manual says about 2012; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.