Alarm code2005

MOTOR TEMPERATURE (0x4310) means the estimated motor temperature rise exceeded the defined alarm limit. The manual's first action is: “Check the motor's rated parameters and load condition. Allow the motor to cool. Ensure the motor cooling system is functioning properly: inspect the cooling fan, clean cooling surfaces, etc. Check the motor thermal model settings (parameters 31.09…31.14).”

Model
ABB ACS850
Display shows
MOTOR TEMPERATURE (0x4310) (2005)
Type
Alarm code
Source
Manual p. 283

What 2005 means

MOTOR TEMPERATURE (0x4310) p. 283

Common causes

  • The estimated motor temperature rise (based on the motor thermal model) exceeds the alarm limit defined by parameter 31.03 Mot temp1 almLim (Motor temperature 1 alarm limit). p. 283

What to do

  1. Check the motor's rated parameters and load condition. Allow the motor to cool. Ensure the motor cooling system is functioning properly: inspect the cooling fan, clean cooling surfaces, etc. Check the motor thermal model settings (parameters 31.09…31.14). p. 283

Before you service the product, read the safety instructions in the manual p. 179.

If 2005 is still not resolved