ABB ACS850 Error 0001: OVERCURRENT (0x2310)

ABB ACS850 · taken from the manufacturer’s manual, pages cited

Fault code0001

Code 0001 indicates output current exceeds the internal fault limit. The manual's first action is: “Check the motor load. Check the acceleration time in parameter group 22 Speed ref ramp. Inspect the motor and motor cables (including phase sequence and delta/star connections). Verify the start-up data in parameter group 99 that correspond to the motor nameplate ratings. Check whether there are power factor correction capacitors or surge absorption devices in the motor cable. Inspect the encoder cable (including phase sequence).”

Model
ABB ACS850
Display shows
OVERCURRENT (0x2310) (0001)
Type
Fault code
Source
Manual p. 290

What 0001 means

OVERCURRENT (0x2310) p. 290

Common causes

  • Output current exceeds the internal fault limit. p. 290

What to do

  1. Check the motor load. Check the acceleration time in parameter group 22 Speed ref ramp. Inspect the motor and motor cables (including phase sequence and delta/star connections). Verify the start-up data in parameter group 99 that correspond to the motor nameplate ratings. Check whether there are power factor correction capacitors or surge absorption devices in the motor cable. Inspect the encoder cable (including phase sequence). p. 290

Before you service the product, read the safety instructions in the manual p. 179.

If 0001 is still not resolved

  • 请联系当地的 ABB 代表 p. 296
    “请联系当地的 ABB 代表”

This page summarises what the manufacturer’s manual says about 0001; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.