BR OVERHEAT (0x7112) means the measured brake resistor temperature exceeded the alarm limit. The manual's first action is: “Stop the inverter. Allow the resistor to cool down. Check the brake resistor overload protection settings (parameters 48.01…48.05). Verify the alarm limit setting, parameter 48.07 Br temp alarmlim. Check that the braking cycle complies with the allowed limits.”
- Model
- ABB ACS850
- Display shows
- BR OVERHEAT (0x7112) (2011)
- Type
- Alarm code
- Source
- Manual p. 284
What 2011 means
BR OVERHEAT (0x7112) p. 284
Common causes
- The measured brake resistor temperature exceeds the alarm value set by parameter 48.07 Br temp alarmlim (brake resistor temperature alarm limit). p. 284
What to do
- Stop the inverter. Allow the resistor to cool down. Check the brake resistor overload protection settings (parameters 48.01…48.05). Verify the alarm limit setting, parameter 48.07 Br temp alarmlim. Check that the braking cycle complies with the allowed limits. p. 284
Before you service the product, read the safety instructions in the manual p. 179.