ABB ACS850 Error 0066: COOLING (0x4290)

ABB ACS850 · taken from the manufacturer’s manual, pages cited

Error code0066

COOLING (0x4290) means the inverter module temperature is too high. The manual's first action is: “Check the setting of parameter 95.03 Temp in u ambient (Maximum ambient temperature). Verify the ambient temperature. If it exceeds 40 °C (104 °F), ensure the load current does not exceed the inverter’s derated load capacity. Refer to the appropriate hardware manual. Check the airflow and fan operation for the inverter module cooling. Inspect the cabinet interior and the inverter module heatsink for dust accumulation and clean if necessary.”

Model
ABB ACS850
Display shows
COOLING (0x4290) (0066)
Type
Error code
Source
Manual p. 296

What 0066 means

COOLING (0x4290) p. 296

Common causes

  • Inverter module temperature is too high. p. 296

What to do

  1. Check the setting of parameter 95.03 Temp in u ambient (Maximum ambient temperature). Verify the ambient temperature. If it exceeds 40 °C (104 °F), ensure the load current does not exceed the inverter’s derated load capacity. Refer to the appropriate hardware manual. Check the airflow and fan operation for the inverter module cooling. Inspect the cabinet interior and the inverter module heatsink for dust accumulation and clean if necessary. p. 296

Before you service the product, read the safety instructions in the manual p. 179.

If 0066 is still not resolved

  • 请联系当地的 ABB 代表 p. 296
    “请联系当地的 ABB 代表”

This page summarises what the manufacturer’s manual says about 0066; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.