Error code0058
FB PAR ERROR (0x6320) means the inverter does not support the function requested by the PLC, or the requested function is not activated. The manual's first action is: “Check the PLC programming. Verify the settings of parameter group 50 Fieldbus.”
- Model
- ABB ACS850
- Display shows
- FB PAR ERROR (0x6320) (0058)
- Type
- Error code
- Source
- Manual p. 295
What 0058 means
FB PAR ERROR (0x6320) p. 295
Common causes
- The inverter does not support the function requested by the PLC, or the requested function is not activated. p. 295
What to do
- Check the PLC programming. Verify the settings of parameter group 50 Fieldbus. p. 295
Before you service the product, read the safety instructions in the manual p. 179.