ABB ACS850 Error 0063: MOTOR TEMP2 (0x4313)

ABB ACS850 · taken from the manufacturer’s manual, pages cited

Alarm code0063

MOTOR TEMP2 (0x4313) means the estimated motor temperature rise exceeds the alarm limit or the measured motor temperature exceeds the alarm value. The manual's first action is: “Check the motor rated parameters and load condition. Allow the motor to cool. Ensure the motor cooling system is functioning: inspect cooling fans, clean cooling surfaces, etc. Verify the alarm limit. Review the motor thermal model settings (parameters 31.09…31.14).”

Model
ABB ACS850
Display shows
MOTOR TEMP2 (0x4313) (0063)
Type
Alarm code
Source
Manual p. 296

What 0063 means

MOTOR TEMP2 (0x4313) p. 296

Common causes

  • The estimated motor temperature rise (based on the motor thermal model) exceeds the alarm limit defined by parameter 31.08 Mot temp2 filtLim (Motor temperature 2 fault limit). p. 296
  • The measured motor temperature exceeds the alarm value set by parameter 31.08 Mot temp2 filtLim. p. 296

What to do

  1. Check the motor rated parameters and load condition. Allow the motor to cool. Ensure the motor cooling system is functioning: inspect cooling fans, clean cooling surfaces, etc. Verify the alarm limit. Review the motor thermal model settings (parameters 31.09…31.14). p. 296
  2. Check that the sensor type matches the actual sensor specified by parameter 31.06 Mot temp2 src (Motor temperature 2 signal source). Check the motor rated parameters and load condition. Allow the motor to cool. Ensure the motor cooling system is functioning: inspect cooling fans, clean cooling surfaces, etc. Verify the alarm limit. p. 296

Before you service the product, read the safety instructions in the manual p. 179.

If 0063 is still not resolved