ABB ACS355 Error 2026: INPUT PHASE LOSS 0309 bit 9 (programmable fault function 3016)

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code2026

Code 2026 means the intermediate circuit DC voltage is oscillating because of a missing input power line phase or blown fuse, with the alarm generated when DC voltage ripple exceeds 14% of nominal DC voltage. The manual's first action is: “Check input power line fuses. Check for input power supply imbalance. Check fault function parameters.”

Model
ABB ACS355
Display shows
2026
Type
Fault code
Source
Manual p. 339

What 2026 means

INPUT PHASE LOSS 0309 bit 9 (programmable fault function 3016) p. 339

Common causes

  • Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. Alarm is generated when DC voltage ripple exceeds 14% of nominal DC voltage. p. 339

What to do

  1. Check input power line fuses. Check for input power supply imbalance. Check fault function parameters. p. 339

Before you service the product, read the safety instructions in the manual p. 239.

If 2026 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”

This page summarises what the manufacturer’s manual says about 2026; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.