Code 2029 means the drive warns that a rotating permanent magnet motor cannot be magnetized with DC current when start mode 2 (DC MAGN) is selected with parameter 2101 START FUNCTION and run is requested. The manual's first action is: “If start to rotating motor is required, select start mode 1 (AUTO) with parameter 2101 START FUNCTION. Otherwise drive starts after motor has stopped.”
- Model
- ABB ACS355
- Display shows
- MOTOR BACK EMF 0309 bit 12 (2029)
- Type
- Fault code
- Source
- Manual p. 339
What 2029 means
MOTOR BACK EMF 0309 bit 12 p. 339
Common causes
- Permanent magnet motor is rotating, start mode 2 (DC MAGN) is selected with parameter 2101 START FUNCTION, and run is requested. Drive warns that rotating motor cannot be magnetized with DC current. p. 339
What to do
- If start to rotating motor is required, select start mode 1 (AUTO) with parameter 2101 START FUNCTION. Otherwise drive starts after motor has stopped. p. 339
Before you service the product, read the safety instructions in the manual p. 239.
If 2029 is still not resolved
- contact your local ABB representative p. 19 “contact your local ABB representative or Authorized Service Center for replacement”