ABB ACS355 Error 1017: PAR SETUP 1 (6320) 0307 bit 15

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code1017

PAR SETUP 1 means only two of the MTAC-01 encoder module, frequency input signal, or frequency output signal can be used simultaneously. The manual's first action is: “Disable frequency output, frequency input or encoder:”

Model
ABB ACS355
Display shows
PAR SETUP 1 (6320) 0307 bit 15 (1017)
Type
Fault code
Source
Manual p. 351

What 1017 means

PAR SETUP 1 (6320) 0307 bit 15 p. 351

Common causes

  • Only two of the following can be used simultaneously: MTAC-01 encoder module, frequency input signal or frequency output signal. p. 351

What to do

  1. Disable frequency output, frequency input or encoder: p. 351
  2. change transistor output to digital mode (value of parameter 1804 TO MODE = 0 [DIGITAL]), or p. 351
  3. change frequency input selection to other value in parameter groups 11 REFERENCE SELECT, 40 PROCESS PID SET 1, 41 PROCESS PID SET 2 and 42 EXT/TRIM PID, or p. 351
  4. disable (parameter 5002 ENCODER ENABLE) and remove MTAC-01 encoder module. p. 351

Before you service the product, read the safety instructions in the manual p. 239.

If 1017 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”