Fault code1017
PAR SETUP 1 means only two of the MTAC-01 encoder module, frequency input signal, or frequency output signal can be used simultaneously. The manual's first action is: “Disable frequency output, frequency input or encoder:”
- Model
- ABB ACS355
- Display shows
- PAR SETUP 1 (6320) 0307 bit 15 (1017)
- Type
- Fault code
- Source
- Manual p. 351
What 1017 means
PAR SETUP 1 (6320) 0307 bit 15 p. 351
Common causes
- Only two of the following can be used simultaneously: MTAC-01 encoder module, frequency input signal or frequency output signal. p. 351
What to do
- Disable frequency output, frequency input or encoder: p. 351
- change transistor output to digital mode (value of parameter 1804 TO MODE = 0 [DIGITAL]), or p. 351
- change frequency input selection to other value in parameter groups 11 REFERENCE SELECT, 40 PROCESS PID SET 1, 41 PROCESS PID SET 2 and 42 EXT/TRIM PID, or p. 351
- disable (parameter 5002 ENCODER ENABLE) and remove MTAC-01 encoder module. p. 351
Before you service the product, read the safety instructions in the manual p. 239.