ABB ACS355 Error 1006: PAR EXT RO (6320) 0307 bit 15

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code1006

PAR EXT RO means incorrect relay output extension parameters. The manual's first action is: “Check parameter settings. Check that following applies: • Output relay extension module MREL-01 is connected to drive. • 1402 RELAY OUTPUT 2, 1403 RELAY OUTPUT 3 and 1410 RELAY OUTPUT 4 have non-zero values. See MREL-01 relay output extension module user's manual (3AUA0000035974 [English]).”

Model
ABB ACS355
Display shows
PAR EXT RO (6320) 0307 bit 15 (1006)
Type
Fault code
Source
Manual p. 350

What 1006 means

PAR EXT RO (6320) 0307 bit 15 p. 350

Common causes

  • Incorrect relay output extension parameters p. 350

What to do

  1. Check parameter settings. Check that following applies: • Output relay extension module MREL-01 is connected to drive. • 1402 RELAY OUTPUT 2, 1403 RELAY OUTPUT 3 and 1410 RELAY OUTPUT 4 have non-zero values. See MREL-01 relay output extension module user's manual (3AUA0000035974 [English]). p. 350

Before you service the product, read the safety instructions in the manual p. 239.

If 1006 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”