PAR PCU 2 means incorrect motor nominal power setting. The manual's first action is: “Check parameter 9909 MOTOR NOM POWER setting. Following must apply: • 1.1 < (9906 MOTOR NOM CURR · 9905 MOTOR NOM VOLT · 1.73 / PN) < 3.0 Where PN = 1000 · 9909 MOTOR NOM POWER (if units are in kW) or PN = 746 · 9909 MOTOR NOM POWER (if units are in hp).”
- Model
- ABB ACS355
- Display shows
- PAR PCU 2 (6320) 0307 bit 15 (1005)
- Type
- Fault code
- Source
- Manual p. 350
What 1005 means
PAR PCU 2 (6320) 0307 bit 15 p. 350
Common causes
- Incorrect motor nominal power setting p. 350
What to do
- Check parameter 9909 MOTOR NOM POWER setting. Following must apply: • 1.1 < (9906 MOTOR NOM CURR · 9905 MOTOR NOM VOLT · 1.73 / PN) < 3.0 Where PN = 1000 · 9909 MOTOR NOM POWER (if units are in kW) or PN = 746 · 9909 MOTOR NOM POWER (if units are in hp). p. 350
Before you service the product, read the safety instructions in the manual p. 239.
If 1005 is still not resolved
- contact your local ABB representative p. 19 “contact your local ABB representative or Authorized Service Center for replacement”