ABB ACS355 Error 1005: PAR PCU 2 (6320) 0307 bit 15

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code1005

PAR PCU 2 means incorrect motor nominal power setting. The manual's first action is: “Check parameter 9909 MOTOR NOM POWER setting. Following must apply: • 1.1 < (9906 MOTOR NOM CURR · 9905 MOTOR NOM VOLT · 1.73 / PN) < 3.0 Where PN = 1000 · 9909 MOTOR NOM POWER (if units are in kW) or PN = 746 · 9909 MOTOR NOM POWER (if units are in hp).”

Model
ABB ACS355
Display shows
PAR PCU 2 (6320) 0307 bit 15 (1005)
Type
Fault code
Source
Manual p. 350

What 1005 means

PAR PCU 2 (6320) 0307 bit 15 p. 350

Common causes

  • Incorrect motor nominal power setting p. 350

What to do

  1. Check parameter 9909 MOTOR NOM POWER setting. Following must apply: • 1.1 < (9906 MOTOR NOM CURR · 9905 MOTOR NOM VOLT · 1.73 / PN) < 3.0 Where PN = 1000 · 9909 MOTOR NOM POWER (if units are in kW) or PN = 746 · 9909 MOTOR NOM POWER (if units are in hp). p. 350

Before you service the product, read the safety instructions in the manual p. 239.

If 1005 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”