ABB ACS355 Error 1009: PAR PCU 1 (6320) 0307 bit 15

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code1009

PAR PCU 1 means incorrect motor nominal speed/frequency setting. The manual's first action is: “Check parameter settings. Following must apply: • 1 < (60 · 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED) < 16 • 0.8 < 9908 MOTOR NOM SPEED / (120 · 9907 MOTOR NOM FREQ / Motor poles) < 0.992”

Model
ABB ACS355
Display shows
PAR PCU 1 (6320) 0307 bit 15 (1009)
Type
Fault code
Source
Manual p. 350

What 1009 means

PAR PCU 1 (6320) 0307 bit 15 p. 350

Common causes

  • Incorrect motor nominal speed/frequency setting p. 350

What to do

  1. Check parameter settings. Following must apply: • 1 < (60 · 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED) < 16 • 0.8 < 9908 MOTOR NOM SPEED / (120 · 9907 MOTOR NOM FREQ / Motor poles) < 0.992 p. 350

Before you service the product, read the safety instructions in the manual p. 239.

If 1009 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”