Code 2010 means the motor temperature is too high or appears to be too high due to excessive load, insufficient motor power, inadequate cooling, or incorrect start-up data, and the measured motor temperature has exceeded the alarm limit set by parameter 3503 ALARM LIMIT. The manual's first action is: “Check motor ratings, load and cooling.”
- Model
- ABB ACS310
- Display shows
- 2010
- Type
- Fault code
- Source
- Manual p. 304
What 2010 means
MOTOR TEMP 0308 bit 9 (programmable fault function 3005...3009 / 3503) p. 304
Common causes
- Motor temperature is too high (or appears to be too high) due to excessive load, insufficient motor power, inadequate cooling or incorrect start-up data. p. 304
- Measured motor temperature has exceeded alarm limit set by parameter 3503 ALARM LIMIT. p. 304
What to do
- Check motor ratings, load and cooling. p. 304
- Check start-up data. p. 304
- Check fault function parameters. p. 304
- Check value of alarm limit. p. 304
- Check that actual number of sensors corresponds to value set by parameter 3501 SENSOR TYPE. p. 304
- Let motor cool down. Ensure proper motor cooling: Check cooling fan, clean cooling surfaces, etc. p. 304
Before you service the product, read the safety instructions in the manual p. 340.
If 2010 is still not resolved
- contact your local ABB representative or Authorized Service Center for replacement p. 17 “contact your local ABB representative or Authorized Service Center for replacement”