Fault code0003
The code means the drive IGBT temperature is excessive. The manual's first action is: “Check ambient conditions. See also section Derating on page 327. Check air flow and fan operation. Check motor power against drive power.”
- Model
- ABB ACS310
- Display shows
- DEV OVERTEMP (4210) 0305 bit 2 (0003)
- Type
- Fault code
- Source
- Manual p. 310
What 0003 means
DEV OVERTEMP (4210) 0305 bit 2 p. 310
Common causes
- Drive IGBT temperature is excessive. Fault trip limit is 135 °C. p. 310
What to do
- Check ambient conditions. See also section Derating on page 327. Check air flow and fan operation. Check motor power against drive power. p. 310
Before you service the product, read the safety instructions in the manual p. 340.
If 0003 is still not resolved
- contact your local ABB representative or Authorized Service Center for replacement p. 17 “contact your local ABB representative or Authorized Service Center for replacement”