ABB ACS310 Error 0003: DEV OVERTEMP (4210) 0305 bit 2

AC drive · taken from the manufacturer’s manual, pages cited

Fault code0003

The code means the drive IGBT temperature is excessive. The manual's first action is: “Check ambient conditions. See also section Derating on page 327. Check air flow and fan operation. Check motor power against drive power.”

Model
ABB ACS310
Display shows
DEV OVERTEMP (4210) 0305 bit 2 (0003)
Type
Fault code
Source
Manual p. 310

What 0003 means

DEV OVERTEMP (4210) 0305 bit 2 p. 310

Common causes

  • Drive IGBT temperature is excessive. Fault trip limit is 135 °C. p. 310

What to do

  1. Check ambient conditions. See also section Derating on page 327. Check air flow and fan operation. Check motor power against drive power. p. 310

Before you service the product, read the safety instructions in the manual p. 340.

If 0003 is still not resolved

  • contact your local ABB representative or Authorized Service Center for replacement p. 17
    “contact your local ABB representative or Authorized Service Center for replacement”

This page summarises what the manufacturer’s manual says about 0003; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.