ABB ACS310 Error 0002: DC OVERVOLT (3210) 0305 bit 1

AC drive · taken from the manufacturer’s manual, pages cited

Fault code0002

The code means there is excessive intermediate circuit DC voltage. The manual's first action is: “Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL). Check input power line for static or transient overvoltage. Check deceleration time (2203, 2206).”

Model
ABB ACS310
Display shows
DC OVERVOLT (3210) 0305 bit 1 (0002)
Type
Fault code
Source
Manual p. 310

What 0002 means

DC OVERVOLT (3210) 0305 bit 1 p. 310

Common causes

  • Excessive intermediate circuit DC voltage. DC overvoltage trip limit is 420 V for 200 V drives and 840 V for 400 V drives. p. 310

What to do

  1. Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL). Check input power line for static or transient overvoltage. Check deceleration time (2203, 2206). p. 310

Before you service the product, read the safety instructions in the manual p. 340.

If 0002 is still not resolved

  • contact your local ABB representative or Authorized Service Center for replacement p. 17
    “contact your local ABB representative or Authorized Service Center for replacement”