Fault code0002
The code means there is excessive intermediate circuit DC voltage. The manual's first action is: “Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL). Check input power line for static or transient overvoltage. Check deceleration time (2203, 2206).”
- Model
- ABB ACS310
- Display shows
- DC OVERVOLT (3210) 0305 bit 1 (0002)
- Type
- Fault code
- Source
- Manual p. 310
What 0002 means
DC OVERVOLT (3210) 0305 bit 1 p. 310
Common causes
- Excessive intermediate circuit DC voltage. DC overvoltage trip limit is 420 V for 200 V drives and 840 V for 400 V drives. p. 310
What to do
- Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL). Check input power line for static or transient overvoltage. Check deceleration time (2203, 2206). p. 310
Before you service the product, read the safety instructions in the manual p. 340.
If 0002 is still not resolved
- contact your local ABB representative or Authorized Service Center for replacement p. 17 “contact your local ABB representative or Authorized Service Center for replacement”