ABB ACS310 Error 0001: OVERCURRENT (2310) 0305 bit 0

AC drive · taken from the manufacturer’s manual, pages cited

Fault code0001

The code means the output current has exceeded the trip level. The manual's first action is: “Check motor load. Check acceleration time (2202 and 2205). Check motor and motor cable (including phasing). Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 327.”

Model
ABB ACS310
Display shows
OVERCURRENT (2310) 0305 bit 0 (0001)
Type
Fault code
Source
Manual p. 310

What 0001 means

OVERCURRENT (2310) 0305 bit 0 p. 310

Common causes

  • Output current has exceeded trip level. p. 310

What to do

  1. Check motor load. Check acceleration time (2202 and 2205). Check motor and motor cable (including phasing). Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 327. p. 310

Before you service the product, read the safety instructions in the manual p. 340.

If 0001 is still not resolved

  • contact your local ABB representative or Authorized Service Center for replacement p. 17
    “contact your local ABB representative or Authorized Service Center for replacement”