The code means the output current has exceeded the trip level. The manual's first action is: “Check motor load. Check acceleration time (2202 and 2205). Check motor and motor cable (including phasing). Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 327.”
- Model
- ABB ACS310
- Display shows
- OVERCURRENT (2310) 0305 bit 0 (0001)
- Type
- Fault code
- Source
- Manual p. 310
What 0001 means
OVERCURRENT (2310) 0305 bit 0 p. 310
Common causes
- Output current has exceeded trip level. p. 310
What to do
- Check motor load. Check acceleration time (2202 and 2205). Check motor and motor cable (including phasing). Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 327. p. 310
Before you service the product, read the safety instructions in the manual p. 340.
If 0001 is still not resolved
- contact your local ABB representative or Authorized Service Center for replacement p. 17 “contact your local ABB representative or Authorized Service Center for replacement”