ABB ACS150 Error A2002: OVERVOLTAGE (programmable fault function, parameter 1610 DISPLAY ALARMS)

ABB ACS150 · taken from the manufacturer’s manual, pages cited

Fault codeA2002

A2002 OVERVOLTAGE means the DC overvoltage controller is active. The manual's first action is: “Check deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2).”

Model
ABB ACS150
Display shows
A2002
Type
Fault code
Source
Manual p. 128

What A2002 means

OVERVOLTAGE (programmable fault function, parameter 1610 DISPLAY ALARMS) p. 128

Common causes

  • DC overvoltage controller is active. p. 128

What to do

  1. Check deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2). p. 128
  2. Check input power line for static or transient overvoltage. p. 128

Before you service the product, read the safety instructions in the manual p. 149.

If A2002 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.