ABB ACS150 Error A2001: OVERCURRENT (programmable fault function, parameter 1610 DISPLAY ALARMS)

ABB ACS150 · taken from the manufacturer’s manual, pages cited

Fault codeA2001

A2001 OVERCURRENT means the output current limit controller is active. The manual's first action is: “Check motor load.”

Model
ABB ACS150
Display shows
A2001
Type
Fault code
Source
Manual p. 128

What A2001 means

OVERCURRENT (programmable fault function, parameter 1610 DISPLAY ALARMS) p. 128

Common causes

  • Output current limit controller is active. p. 128

What to do

  1. Check motor load. p. 128
  2. Check acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). p. 128
  3. Check motor and motor cable (including phasing). p. 128
  4. Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 138. p. 128

Before you service the product, read the safety instructions in the manual p. 149.

If A2001 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.