A2026 INPUT PHASE LOSS means an alarm is generated when DC voltage ripple exceeds 14% of nominal DC voltage due to a missing input power line phase or blown fuse. The manual's first action is: “Drive output current is limited and alarm INPUT PHASE LOSS (code: A2026) is generated when the DC voltage ripple exceeds 14% of the nominal DC voltage. There is a 10 s delay between the activation of the alarm and the output current limitation. The current is limited until the ripple drops under the minimum limit, $0.3 imes I_{hd}$.”
- Model
- ABB ACS150
- Display shows
- INPUT PHASE LOSS (A2026)
- Type
- Fault code
- Source
- Manual p. 111
What A2026 means
INPUT PHASE LOSS p. 111
Common causes
- DC voltage ripple exceeds 14% of the nominal DC voltage. p. 111
- Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. Alarm is generated when DC voltage ripple exceeds 14% of nominal DC voltage. p. 111
What to do
- Drive output current is limited and alarm INPUT PHASE LOSS (code: A2026) is generated when the DC voltage ripple exceeds 14% of the nominal DC voltage. There is a 10 s delay between the activation of the alarm and the output current limitation. The current is limited until the ripple drops under the minimum limit, $0.3 imes I_{hd}$. p. 111
- Check input power line fuses. Check for input power supply imbalance. Check fault function parameter setting. p. 111
Before you service the product, read the safety instructions in the manual p. 149.
If A2026 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.