ABB ACS150 Error F0022: INPUT PHASE LOSS

ABB ACS150 · taken from the manufacturer’s manual, pages cited

Fault codeF0022

F0022 INPUT PHASE LOSS means DC voltage ripple is excessive due to a missing input power line phase or blown fuse, causing a fault trip when ripple exceeds 14% of nominal DC voltage. The manual's first action is: “The drive trips on fault INPUT PHASE LOSS (code: F0022) and the motor coasts to stop when the DC voltage ripple exceeds 14% of the nominal DC voltage.”

Model
ABB ACS150
Display shows
INPUT PHASE LOSS (F0022)
Type
Fault code
Source
Manual p. 111

What F0022 means

INPUT PHASE LOSS p. 111

Common causes

  • DC voltage ripple is excessive. p. 111
  • Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. Fault trip occurs when DC voltage ripple exceeds 14% of nominal DC voltage. p. 111

What to do

  1. The drive trips on fault INPUT PHASE LOSS (code: F0022) and the motor coasts to stop when the DC voltage ripple exceeds 14% of the nominal DC voltage. p. 111
  2. Check input power line fuses. Check for input power supply imbalance. Check fault function parameter setting. p. 111

Before you service the product, read the safety instructions in the manual p. 149.

If F0022 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.