F0022 INPUT PHASE LOSS means DC voltage ripple is excessive due to a missing input power line phase or blown fuse, causing a fault trip when ripple exceeds 14% of nominal DC voltage. The manual's first action is: “The drive trips on fault INPUT PHASE LOSS (code: F0022) and the motor coasts to stop when the DC voltage ripple exceeds 14% of the nominal DC voltage.”
- Model
- ABB ACS150
- Display shows
- INPUT PHASE LOSS (F0022)
- Type
- Fault code
- Source
- Manual p. 111
What F0022 means
INPUT PHASE LOSS p. 111
Common causes
- DC voltage ripple is excessive. p. 111
- Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. Fault trip occurs when DC voltage ripple exceeds 14% of nominal DC voltage. p. 111
What to do
- The drive trips on fault INPUT PHASE LOSS (code: F0022) and the motor coasts to stop when the DC voltage ripple exceeds 14% of the nominal DC voltage. p. 111
- Check input power line fuses. Check for input power supply imbalance. Check fault function parameter setting. p. 111
Before you service the product, read the safety instructions in the manual p. 149.
If F0022 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.