Introduces the use of TOSVERT VF-AS1 series RS485 communication function
This document serves as an instruction manual for the RS485 communication function provided on the TOSVERT VF-AS1 series of industrial inverters. It covers both two-wire and four-wire RS485 communication ports and explains how to establish links between computers and inverters or enable inter-drive communication for proportional control without a host computer.
The manual describes two supported communication protocols: the TOSHIBA Inverter Protocol and the MODBUS-RTU Protocol. It provides detailed specifications for data transmission, including baud rates, character formats (ASCII and Binary), and error detection methods. Furthermore, it outlines specific commands for monitoring inverter status, issuing run/stop commands, and setting parameters, along with examples of communication programs and troubleshooting guides.
| Transmission scheme | Half-duplex |
|---|---|
| Communication baud rate | 9600/19200/38400 bps |
| Character transmission format (ASCII mode) | JIS X 0201 8-bit |
| Character transmission format (Binary mode) | Binary codes fixed to 8 bits |
| Stop bit length (Received) | 1 bit |
| Stop bit length (Sent) | 2 bits |
The inverter supports the TOSHIBA Inverter Protocol and the MODBUS-RTU Protocol.
The initial value for the communication protocol selection parameter is set to 0, which corresponds to the TOSHIBA protocol.
Yes, the inter-drive communication function allows proportional control of inverters on the same network without using a host computer.