Rockwell Automation 1756 ControlLogix Chassis and Power Supplies Product Information
This two-page Rockwell Automation publication covers environment and enclosure information for 1756 ControlLogix chassis and power supplies. It explains the North American hazardous location approval for products marked “CL I, DIV 2, GP A, B, C, D” and how the temperature code of a system may be determined when products are combined.
The document also describes European hazardous location approval for products marked II 3 G, including the type of protection and conditions for use in Zone 2. Warnings cover explosion hazard precautions, enclosure requirements such as IP54 in Zone 2, use of ATEX certified Rockwell Automation backplanes, and the surrounding air temperature ranges that apply to XT, LXT and non-XT equipment.
Rockwell Automation 1756 ControlLogix specifications
| Surrounding air temperature range, XT equipment | -25…70 °C (-13…158 °F) |
|---|---|
| Surrounding air temperature range, LXT equipment | -25…60 °C (-13…140 °F) |
| Surrounding air temperature range, non-XT equipment | 0…60 °C (32…140 °F) |
| Altitude without derating | up to 2000 m (6562 ft) |
| Pollution degree | 2 |
| Overvoltage category | II |
| Enclosure protection in Zone 2 | at least IP54 |
| Type of protection (II 3 G products) | Ex nA IIC T- or Ex nC IIC T- |
Source: Rockwell Automation 1756 ControlLogix Chassis and Power Supplies Product Information
All Rockwell Automation 1756 ControlLogix documents by type
Mounting, wiring and first power-up. Read it before the hardware goes in.
Ratings, dimensions and ordering codes, for selection and design work.
Questions answered in these manuals
What hazardous locations are products marked “CL I, DIV 2, GP A, B, C, D” suitable for?
They are suitable for use in Class I Division 2 Groups A, B, C, D hazardous locations and nonhazardous locations only.
From: Rockwell Automation 1756 ControlLogix Chassis and Power Supplies Product Information
What enclosure protection is required when the equipment is applied in Zone 2 environments?
The equipment must be installed in an enclosure providing at least IP54 protection.
From: Rockwell Automation 1756 ControlLogix Chassis and Power Supplies Product Information
What enclosure protection is required for Zone 2 environments?
Equipment must be installed in an enclosure that provides at least IP54 protection.
From: Rockwell Automation 1756 ControlLogix Controllers Environment and Enclosure
What are the requirements for the enclosure's flame-retardant properties?
The enclosure must have a flame spread rating of 5VA or be approved for the application if it is nonmetallic.
From: Rockwell Automation 1756 ControlLogix Controllers Environment and Enclosure
What chassis are compatible with these power supplies?
These power supplies are compatible with Series A, Series B, and Series C 1756 chassis.
From: Rockwell Automation 1756 ControlLogix Power Supplies Specifications
What is the maximum non-operating shock value for Series C chassis?
The maximum non-operating shock value for Series C chassis is limited to 30 g.
From: Rockwell Automation 1756 ControlLogix Power Supplies Specifications