Rockwell Automation PowerFlex 400 Adjustable Frequency AC Drive Quick Start Guide
This Quick Start Guide provides a summary of the basic steps necessary to install, start up, and program the PowerFlex 400 Adjustable Frequency AC Drive. The information provided does not replace the User Manual and is intended only for qualified personnel responsible for performing maintenance on the drive.
The document includes critical safety precautions, such as waiting three minutes for high-voltage capacitors to discharge before working on the drive. It also covers general installation considerations, including mounting the drive vertically on a flat surface, protecting the cooling fan from dust, and avoiding corrosive atmospheres. Specific mounting requirements for different drive structures (C, D, E, F) are detailed, including enclosure ratings and minimum clearances. This manual is written in Spanish.
Rockwell Automation PowerFlex 400 FRN 4.xx specifications
| Output Power Rating (Catalog 22C-B012N103) | 2.2 kW (3.0 HP) |
|---|---|
| Input Voltage Range | 200‑240 V AC – 3‑Phase |
| Maximum Surrounding Air Temperature | -10 °C to 45 °C (14 °F to 113 °F) |
| Control Output Frequency Range | 0‑320 Hz (programmable) |
| Electrical Efficiency at Rated Current | 97.5 % |
Source: Rockwell Automation PowerFlex 400 FRN 4.xx Quick Start Guide
All Rockwell Automation PowerFlex 400 FRN 4.xx documents by type
The shortest path to a working setup, usually only a few pages.
Questions answered in these manuals
How long must I wait after disconnecting power before working on the drive?
You must wait three minutes for the capacitors to discharge to safe voltage levels.
From: Rockwell Automation PowerFlex 400 Adjustable Frequency AC Drive Quick Start Guide
What is the maximum ambient air temperature rating for Structure C drives?
The maximum surrounding air temperature is 45°C (113°F) for Option A and 50°C (122°F) for Option B.
From: Rockwell Automation PowerFlex 400 Adjustable Frequency AC Drive Quick Start Guide
How do I clear a fault on the PowerFlex 400 drive?
Press the Stop key, cycle power, or set parameter A100 (Fault Clear) to 1 or 2.
From: Rockwell Automation PowerFlex 400 FRN 4.xx Quick Start Guide
What safety precaution must be taken before working on the drive?
Ensure the mains supply is isolated and wait three minutes for the high‑voltage capacitors to discharge.
From: Rockwell Automation PowerFlex 400 FRN 4.xx Quick Start Guide