Key facts
- Brand
- Mitsubishi Electric
- Model
- FR-A802
- Category
- inverter
- Documents
- 2
- Languages
- ZH · EN
- Last added
- 2023-11-07
Start here

Mitsubishi Electric FR-A802 Variable Frequency Drive Hardware Manual
This hardware manual covers the Mitsubishi Electric FR-A802 variable frequency drive in the separated-rectifier configuration. It states that the manual describes hardware operations such as installation and wiring that differ from the FR-A800, while basic operation parameters and other software details are in the FR-A800 detailed manual on the included CD-ROM.
The document also provides safety precautions for transportation, installation, wiring, trial operation, operation, troubleshooting, maintenance, and disposal, including precautions for PM motors and protective functions. This manual is written in Chinese.
Mitsubishi Electric FR-A802 specifications
| Ambient temperature (LD/MD/ND ratings) | -10 to +50°C, no freezing |
|---|---|
| Ambient humidity | 95%RH or less, no condensation |
| Altitude | 2500 m or less |
| Vibration | 2.9 m/s² or less; 10–55 Hz in X, Y, and Z directions |
Source: Mitsubishi Electric FR-A802 Variable Frequency Drive Hardware Manual
All Mitsubishi Electric FR-A802 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What must be done before wiring or inspection?
After confirming the operation panel indicator is off, turn off the power, wait at least 10 minutes, and check the residual voltage with a multimeter before wiring or inspection.
From: Mitsubishi Electric FR-A802 Variable Frequency Drive Hardware Manual
What is the ambient humidity limit?
The inverter must be used at an ambient humidity of 95%RH or less, without condensation.
From: Mitsubishi Electric FR-A802 Variable Frequency Drive Hardware Manual
How do I set the inverter for single wound motor parallel operation?
Set Pr.1001 to "200" on the master station and "1 or 2" on the slave station.
From: Mitsubishi Electric FR-A802-P Inverter Parallel Operation Function Manual
How do I set the inverter for multi-wound motor parallel operation?
Set Pr.1001 to "10200" on the master station and "10201" on the slave station.
From: Mitsubishi Electric FR-A802-P Inverter Parallel Operation Function Manual