Kyoritsu 4118A Digital PSC-Loop Tester Instruction Manual
This manual provides detailed instructions for operating the Kyoritsu 4118A digital PSC-loop tester, including safety precautions, instrument layout, test lead specifications, and measurement procedures for loop impedance and prospective short-circuit current. It also covers operating conditions, safety categories, and troubleshooting.
The tester is designed for single-phase AC systems (230V) and supports both phase-to-earth and OLD-TT system phase-to-neutral measurements. It features overload and overheat protection, manual and auto-test modes, and displays measurements in ohms and amperes with 3 1/2-digit resolution. This manual is written in Chinese.
Kyoritsu 4118A specifications
| Measurement Range - Loop Impedance | 0.00–19.99 Ω / 0.0–199.9 Ω / 0–1999 Ω |
|---|---|
| Measurement Range - Prospective Short-Circuit Current | 0.0–199.9A / 0–1999A / 0.00–19.99kA |
| Operating Temperature | 0 to +40℃ |
| Storage Temperature | −20 to +60℃ |
| Dimensions | 186×167×89mm |
| Weight | 750g |
| Power Source | 230V, 50Hz |
| Protection Degree | IP 54 |
Source: Kyoritsu 4118A Digital PSC-Loop Tester Instruction Manual
All Kyoritsu 4118A documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the measurement range for loop impedance?
The loop impedance range is 0.00–19.99 Ω, 0.0–199.9 Ω, and 0–1999 Ω.
From: Kyoritsu 4118A Digital PSC-Loop Tester Instruction Manual
How does the tester handle RCDs during testing?
For models 4118A without D-LOK circuitry, all RCDs (RCCB, ELCB) must be bypassed during testing, except on the loop-2000Ω range.
From: Kyoritsu 4118A Digital PSC-Loop Tester Instruction Manual
What is the D-LOK circuit?
The D-LOK circuit is an automatic device (RCD) lock that avoids the need to by-pass most RCD's during testing.
From: Kyoritsu 4116A/4118A/4120A Digital PSC-Loop Tester Instruction Manual
How do the wiring check LEDs work?
The P-E and P-N LEDs illuminate when wiring polarity is correct, while the Reverse LED lights up when P and N are reversed.
From: Kyoritsu 4116A/4118A/4120A Digital PSC-Loop Tester Instruction Manual
What is the maximum current measurement capability?
The device can measure up to 4.0kA with a response time of 25A/20ms.
From: Kyoritsu 4116A/4118A/4120A Loop Resistance Tester User Manual
What are the operating temperature conditions?
The unit operates within a range of -20 to 60 degrees Celsius.