APC Smart-UPS RC XLI/XLICH/XLI-CC 1000/2000/3000 VA User Manual
The APC Smart-UPS RC is a high-performance uninterruptible power supply (UPS) designed to protect electronic equipment from power outages, voltage sags, brownouts, and surges. It features double-conversion online technology to ensure continuous power and includes battery backup capabilities. This manual is written in Chinese.
Read onlineAPC 3000 VA specifications
| System Capacity (2400VA Model) | 2400VA or 1680W whichever limit is reached first |
|---|---|
| System Capacity (3000VA Model) | 3000VA or 2100W whichever limit is reached first |
| Efficiency | at least 91% |
| Input Nominal Voltage (120VAC models) | 120VAC |
| Input Nominal Voltage (100VAC models) | 100VAC |
| Output Connectors (2400VA models) | 3 NEMA 5-15R; 2 NEMA 5-20R; 1 NEMA L5-20R |
| Output Connectors (3000VA models) | 6 NEMA 5-15R; 2 NEMA 5-20R |
| Operating Ambient Temperature | +32 °F to 104 °F (0°C to 40°C) |
Source: APC Smart-UPS RT 2400VA and 3000VA Guide Specifications
All APC 3000 VA documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
- APC Smart-UPS 2200/3000 VA 100/120/230 VAC Tower UPS User Manual 17 p
- APC Smart-UPS RC XLI/XLICH/XLI-CC 1000/2000/3000 VA User Manual 21 p
- APC Smart-UPS 2200 VA 120/230 Vac 3000 VA 100/120/208/230 Vac Rack 2U User Manual 21 p
- APC Smart-UPS XL 2200/3000 VA User Manual 19 p
- APC Smart-UPS C 1000/1500/2000/3000 VA 120/230 Vac Rack-Mount 2U Operation Manual 20 p
- Smart-UPS 750/1000/1500/2200/3000 VA 120/230 V ac online UPS User Guide 21 p
- APC Smart-UPS 2200VA/3000VA 2U Rack-Mount UPS User Manual 16 p
Questions answered in these manuals
Is the battery system user-replaceable?
Yes, the UPS batteries are modular, hot-swappable, and user-replaceable.
From: APC Smart-UPS RT 2400VA and 3000VA Guide Specifications
What is the minimum input power factor?
The input power factor is a minimum of 0.95 lagging at 100% load at nominal voltage.
From: APC Smart-UPS RT 2400VA and 3000VA Guide Specifications
How often does the UPS perform a self-test by default?
The UPS performs a self-test automatically when it is turned on and every two weeks (168 hours) by default.
From: APC Smart-UPS 2200/3000 VA 100/120/230 VAC Tower UPS User Manual
What is the purpose of the TVSS screw on the back panel?
The TVSS screw is used to connect ground wires from surge suppressors for telephone and network lines.
From: APC Smart-UPS 2200/3000 VA 100/120/230 VAC Tower UPS User Manual
What is the operating temperature range for the Smart-UPS RC?
The operating temperature range is 0° to 40°C.
From: APC Smart-UPS RC XLI/XLICH/XLI-CC 1000/2000/3000 VA User Manual
What is the maximum altitude for operating the UPS?
The maximum operating altitude is 3,000 meters.
From: APC Smart-UPS RC XLI/XLICH/XLI-CC 1000/2000/3000 VA User Manual