Victaulic FireLock automatic sprinkler installation and maintenance instructions covering safety warnings, installation steps, torque values, and inspection.
This document provides installation and maintenance instructions for Victaulic FireLock automatic sprinklers. It lists safety warnings and requirements for depressurizing and draining piping, verifying the sprinkler model, orifice size and temperature rating, and following NFPA, FM, VdS, CEA 4001, and local codes.
Standard sprinkler installation steps cover inspecting the sprinkler and glass bulb, installing recessed collars, applying pipe-joint compound to male threads, tightening with the proper sprinkler wrench, and removing bulb or link protectors before service. A table gives maximum assembly torque values by NPT orifice size, and the text describes inspection, cleaning, and replacement requirements.
| Maximum assembly torque, 1/2-inch NPT | 14 ft-lbs/19 N•m |
|---|---|
| Maximum assembly torque, 3/4-inch NPT | 20 ft-lbs/27 N•m |
| Maximum assembly torque, 1-inch NPT | 30 ft-lbs/41 N•m |
The piping system must be completely depressurized and drained immediately before installation, removal, adjustment, or maintenance.
No. Sprinklers must not be painted, coated, plated, or altered.
Remove it with a soft, dry cloth; do not use soapy water, detergents, ammonia, cleaning fluids, or other chemicals.
The maximum assembly torque is 20 ft-lbs/27 N•m.