This guide provides installation, commissioning, and alarm testing instructions for the FireLock NXT 768N steam valve with SBSC trim.
This document serves as a guide for putting the FireLock NXT 768N steam valve system into operation and performing alarm tests. It details the step-by-step procedures for system preparation, charging with air, draining, and verifying normal operating states for various valves in the assembly.
The guide specifies that an experienced and trained installer must study the installation, maintenance, and testing manual before operating the system. It includes a table of normal operating positions for all valves and outlines the necessary alarm test procedure for water flow, referencing NFPA 25 and local regulations. This manual is written in Swedish.
| Maximum Air Pressure | 20 psi/138 kPa/1,4 bar |
|---|
The procedure involves notifying authorities, flushing the supply, closing the drain valve, opening the alarm test valve to activate alarms, and checking for leaks.
All system drains must be closed and the system must be leak-free.
13 psi/90 kPa/0.9 bar.
20 psi/138 kPa/1.4 bar.