This manual provides instructions for the installation, maintenance, and testing of the 769N Series FireLock NXT™ Deluge Valves for air (dry-actuated), liquid (wet-actuated), and electric release systems.
This Victaulic manual is for the 769N Series FireLock NXT deluge valves for pneumatic (dry pilot), hydraulic (wet pilot), and electric release systems. It states that the valves are only for fire systems, that system design and installation must follow applicable NFPA 13, 13D, and 13R standards or equivalents and applicable building and fire codes, and that the instructions are for trained, experienced installers. It also warns to confirm that the piping system is fully depressurized and drained before installing, removing, adjusting, or maintaining a Victaulic product, and to wear eye, head, and foot protection.
The manual includes piping dimensions, exploded views for pneumatic, hydraulic, and electric release piping, internal valve component views, air supply requirements, hydrostatic testing, initial system setup, resetting the system, weekly and monthly external checks, required main drain, waterflow alarm, water level and low air pressure alarm, partial operation, and full operation tests, internal inspection, diaphragm and clapper component replacement, cleaning, filter replacement, and troubleshooting. This manual is written in Chinese.
| Maximum working pressure | 300 psi/2065 kPa/20.7 Bar |
|---|---|
| Factory test pressure | 600 psi/4135 kPa/4.1 Bar |
| Minimum air pressure for dry pilot release system | 13 psi/90 kPa/0.9 Bar |
The maximum working pressure is 300 psi/2065 kPa/20.7 Bar.
The factory test pressure is 600 psi/4135 kPa/4.1 Bar for all sizes.
The minimum air pressure for the dry pilot release system is 13 psi/90 kPa/0.9 Bar.