About this manual

This operation manual covers the TOYO-F40 digital multifunction protection relay, a microprocessor-based device with a withdrawable case and RS-485 interface. It shows phase voltage, current, phase angle, power, and energy, and supports definite-time and inverse-time protection curves.

The relay stores up to 1024 event records and six waveform records, with a CB trip counter up to 65,535. A 4x20 LCD and front-panel keys provide access to measurement, status, record, system information, protection setting, CB control, contact planning, date/time, and communication menus. This manual is written in Chinese.

What's inside

  • Model and main functions
  • Panel items
  • Relay page overview
  • Measurement
  • Status
  • Records
  • System information
  • Protection settings
  • CB control
  • Communication settings

Specifications

ModelTOYO-F40
Working power supplyAC/DC 80~260V
Event record capacity1024 entries
Waveform record capacity6 records
Waveform record length168 cycle fixed
CB trip counter maximum65535
Display4x20 LCD
Communication interfaceRS-485

Frequently asked questions

What protection curves does the TOYO-F40 support?

It supports definite-time and inverse-time curves, including normal, very, and extremely inverse types.

How many event records can the TOYO-F40 store?

It can store up to 1024 event records, including pickup, trip, reset, setting change, and power on/off information.

What is the working power supply of the TOYO-F40?

It uses an AC/DC 80~260V dual-use power supply.

Does the TOYO-F40 provide an RS-485 output?

Yes, it provides RS-485 output for central monitoring.