This manual explains in detail the OPCN66-Z communication protocol for VF66 inverters.
This manual details the communication protocol for the OPCN66-Z option board used with Toyo VF66B inverters. It covers safety precautions, terminal specifications, communication modes, and supported services like data read/write and reset. The protocol conforms to JIS B 3511:1999 (JEM-F 3008:1999) for OPCN-1 communication. Users must follow safety guidelines and wiring instructions to avoid electric shock or equipment damage.
The manual also explains how to configure the board’s communication settings, including station number and mode (conformity or non-conformity), and lists supported network services such as initial setting, input/output, and data read/write. It references additional manuals for terminal block functions and inverter setup.
| Connection Type | Bus type (Multi-drop system) |
|---|---|
| Transmission Speed | 125kpbs - 1000m or less |
| Error Check System | 16 bits FCS (Frame check sequence) by a Cyclic Redundancy Check (CRC-CCITT) |
It supports 1 to 31 slave stations against one master station.
The default mode is 'conformity mode' as per JIS standard.
Turn ON SW3 on the OPCN66-Z board after turning off the inverter.